Construction Process Plan of Landscape Light Installation
1、 Laying of wire pipe and steel pipe:
(1)
The design selects concealed laying of wire pipe and steel pipe, and the
construction is carried out according to the construction process standard of
wire pipe and steel pipe laying sub project. The purchase of wire pipe and
steel pipe shall be strictly closed, and the junction box, light head box,
switch box, etc. shall be provided with product certificate.
(2)
The embedded pipe shall be closely coordinated with the civil construction,
first to meet the layout of the water pipe, and then to arrange the electrical
piping according to the location.
(3)
Outdoor power distribution lines shall be laid underground through HDPE pipes
with a buried depth of 0.7m. When crossing water system, the buried depth shall
not be less than 0.5m. When crossing motorway, the cables shall be laid through
steel pipes. L500.w300.h700 crossing well shall be set beside the courtyard light
when the courtyard light line meets branch, and reliable waterproof measures
shall be taken at all line branches (such as ip62 waterproof junction box).
Two.
Threading:
The
incoming of wires shall be strictly controlled for threading in the pipe. The
specification and model of wires must meet the design requirements and have the
factory certificate. After arrival, check whether the insulation resistance,
diameter of wire core, material and weight of each coil meet the requirements.
The mouth protector of response specification shall be selected according to
the size of pipe diameter, and the specifications and materials of nylon
crimping cap and wiring nose shall meet the requirements. The threading in the
pipe shall be carried out after the completion of the construction work of the
building structure and civil engineering. Firstly, the threading shall be
carried out with Φ 1.2-2.0mm iron wire, with a margin of 10-15cm at both ends,
and then the soil and dust of the pipe, switch box, socket box, etc. shall be
cleaned. When threading, pay attention to that the wires of the same AC circuit
must be threaded in the same tube, and the wires of different circuits,
different voltages and AC and straight lines shall not be threaded in the same
tube, except for the following situations: the circuit with standard voltage
below 50V; the power circuit of the same equipment or the same flow line
equipment and the control circuit without special anti-interference
requirements; several circuits of the same lantern Several circuits of the same
kind of lighting, but the total number of conduits in the pipe shall not be
more than 8. Reserved length of Conductor: 15cm for junction box, switch box,
socket box and light head box, and 1 / 2 of the perimeter of box in
distribution box.
(1)
lights and light sources shall be used according to the design requirements.
All lights shall be provided with product certificates. Wiring in lights shall
not be exposed, and lights and accessories shall be complete.
(2)
According to the installation site, check whether the lights meet the
requirements, and check the wiring inside the lights. The lights must be
installed firmly, in the correct position, neat and beautiful, and the wiring
is correct. For lights above 3kg, magnesium hooks or bolts must be pre
installed, and the metal shell of lights below 2.4m shall be well grounded.
(3)
After the installation, the insulation resistance of each branch shall be
measured by telemetering, and then the power on operation is allowed. After
power on, carefully check whether the control of the light is flexible and
ready. The switch corresponds to the control sequence of the light. If any
problem is found, power off first, and then find out the cause for repair.
4、 Grounding protection and safety
measures:
(1)
The grounding protection adopts TT mode. A closed ring artificial grounding
device is set around the outdoor lighting box. The grounding electrode adopts
50 * 50 * 5l2500 hot-dip galvanized angle steel, and the connecting wire adopts
40 * 4 hot-dip galvanized flat steel. The grounding electrode spacing is 5m,
the buried depth is 0.8m, and the grounding resistance is not more than 10
ohms.
(2)
All lighting grounding terminals in the system shall be reliably connected with
PE bus of lighting box and grounded after being reliably connected with PE
line.
(3)
In order to prevent lightning over voltage, primary surge protector is set in
outdoor lighting box.